Power Frequency Tests of Bushing
- Power Factor Test
- Partial Discharge Test
- Wet Power Frequency Voltage withstand Test
- Momentary Power Frequency Voltage Withstand Test
- Visible Discharge Test
Power Factor Test
- High voltage Schering bridge is used for this test. The test setup is shown in Figure A.
- The conductor coming from bushing is connected to HV source and transformer tank is connected to detector (D) side as shown.
- The Schering bridge is balanced by usual procedure.
- The observations are taken with increasing, and decreasing values of voltages.
- The power factor (cos Φ), capacitance of bushing (C2) is evaluated for each observation.
- The loss factor (tan 𝛿) is calculated.
Figure A |
The characteristics of tan 𝛿 and applied voltage is plotted.
Figure B |
Potential Discharge Test
The test setup is shown in Figure C.
- The bushing to be tested is connected across sphere gap.
- The cascade transformer produces high voltage which is applied to bushings.
- If any partial discharge activity takes place, in bushing due to voids, cracks etc, it is recorded by PD measurement circuit.
Wet Power Frequency Voltage Withstand Test
- These tests are applicable to outdoor, indoor and outdoor immersed bushings up to 245 kV ratings.
- Duration of test is 60 seconds.
- The test is conducted in accordance with 1.5.2071 (Part 2) 1976. Before the commencement of the test, the bushings is exposed to the atmospheric condition specified in I.S.
- The bushings is considered to have passed the test if no flashover or puncture occurs.
- If there is puncture the bushing is considered to failed the test.
- If flashover occurs the test is repeated only once.
- If during the repetition of the test, no flashover or puncture occurs the bushing is considered to have passed the test.
Momentary Power Frequency Voltage Withstand Test
- The test voltage as mentioned in IS is applied to bushing for 30 seconds.
- The bushing has to withstand this voltage without flashover or puncture.
Visible Discharge Test
- This test is performed in dark room because the discharge taking place is not visible in light.
- Standard test voltage is applied to the bushing.
- No discharge should take place on the bushings.
- The discharge taking place on arcing horns, grading rings of bushing is permitted.
- The radio interference occurring due to this is also measured using suitable arrangement.