Other Test of Circuit Breakers

Other Test of Circuit Breakers

  1. Temperature Rise Test
  2. Mechanical Test
1. Temperature Rise Test

Temperature Rise Test Circuit
Figure A

Measuring Temperature by Thermocouple
Figure B

For measuring temperature to find temperature rise either thermocouples, self resistance method or thermometer is used:
In the above circuit thermocouple is used :

  • In the test circuit a special transformer is used.
  • This transformer has primary 230 V to 440 Volts rating when secondary voltage is of 5 to 15 volts.
  • The test voltage is adjusted by regulator.
  • By regulating the voltage a required continuous high current is sent to the test terminals.
  • The high current is measured by C.T. Current produces heating effect and temperature increases . Temperature (T) is measured by thermocouple or thermometer.
  • Ambient temperature is known (Ta).

∴ Temperature rise = T – Ta is found.

  • The rated voltage with rated frequency is applied in the circuit.
  • A continuous current is passed till steady temperature is reached. The readings of temperature of various conducting, insulating and structure parts are taken every after 1/2 Hr or 1Hr.
  • The maximum temperature of the parts shall be within the prescribed limits.
  • The thermocouple comprises a junction of two dissimilar materials.
  • The emf induced depends upon temperature difference between the hot junction and the cold end.
  • The hot junctions on fixed on the parts of isolator (contacts of isolators, terminals insulators etc.)
  • The output of thermocouple is measured by potentiometer or digital voltmeter.
  • The temperature is calculated for the calibrated value (°C per Milivolts)

2. Mechanical Test

  • This is for testing reliability of mechanical operation of isolator.
  • The isolator contacts are opened and closed several times.
  • The contacts are closed and opened by usual way (manual or motorized) After this test, all contacts, linkages, are thoroughly checked.
  • The dimensions of all these should be in original limits.
  • If any part has failed mechanically, the dimensions are out of permissible limits.
  • Generally 1000 close-open cycles are specified in standards.
Measuring Temperature by Thermocouple