Power Frequency Tests of Bushing

Power Frequency Tests of Bushing Power Factor Test Partial Discharge Test Wet Power Frequency Voltage withstand Test Momentary Power Frequency Voltage Withstand Test Visible Discharge Test Power Factor Test High voltage Schering bridge is used for this test. The test setup is shown in Figure A. The conductor coming from bushing is connected to HV … Read more

Testing of Bushings

Testing of Bushings Q. Describe in brief various tests carried out on ‘Bushings’. Bushings are insulators that are generally used on high voltage side of transformer. H.V. side connection The bushing is hollow and half of its portion enters transformer tank as shown. The HV winding connections are carried through bushings and brought out from … Read more

Other Tests of Insulators

Other Tests of Insulators Temperature Cycle Test Pollution Test 1. Temperature Cycle Test Insulators with their integral parts shall be quickly and completely immersed without being placed in an intermediate container in a water bath. The temperature is maintained at 70°C higher than that of the cold bath (used in the rest of the test). … Read more

Measurement of Partial Discharge

Measurement of Partial Discharge Requirements of Partial Discharge Measuring System Most important parameters is apparent charge. The discharge current IC(t) is quantified over small duration of time hence it is called apparent charge. External noise may cause interference with this PD current pulses giving wrong results. So proper filters are necessary. The recorded pulses of PD should … Read more

Loss Measurement on Complete Equipment/Schering Bridge with Faraday Cage

Loss Measurement on Complete Equipment/Schering Bridge with Faraday Cage It is used to measure dielectric loss. It is particularly suitable for the insulation specimen whose one side is permanently earthed. There are two methods subjected for such measurements. (A) Inversion of the ‘Schering bridge using Faraday cage.(B)  Use of artificial earth fully screened bridge. (A) … Read more

Impulse Tests of Insulators

Impulse Tests of Insulators Impulse Voltage Withstand Test Impulse Flashover Test 1. Impulse Voltage Withstand Test The test setup is shown in Figure. The impulse generator is adjusted to produce a standard 1.2/50 impulse wave of peak value equal to the specified value of the impulse withstand voltage corrected for atmosphere conditions in accordance with … Read more