Power Frequency Test

Power Frequency Test

Power Frequency Sparkover Test (Dry and Wet)

The test setup is shown in Figure.

Power Frequency Test on Surge Arrester
  1. A standard voltage source is used. This source is connected between live terminal and earth terminal of surge arrester.
  2. A voltage of 1.5 times rated voltage is applied to surge arrester consecutively for 5 times.
  3. Sparkover should not occur during application voltages.
  4. If sparkover occurs, the current flow is large, so a current limiting resistance R is connected. Which limits the current to safe value.