Other Test of Testing Isolators
- Temperature Rise Test (Heat Run Test)
- Mechanical Test (Endurance Test)
1. Temperature Rise Test (Heat Run Test)
Figure A |
Figure B |
For measuring temperature to find temperature rise either thermocouples, self resistance method or thermometer is used:
In the above circuit thermocouple is used :
In the above circuit thermocouple is used :
- In the test circuit a special transformer is used.
- This transformer has primary 230 V to 440 Volts rating when secondary voltage is of 5 to 15 volts.
- The test voltage is adjusted by regulator.
- By regulating the voltage a required continuous high current is sent to the test terminals.
- The high current is measured by C.T. Current produces heating effect and temperature increases . Temperature (T) is measured by thermocouple or thermometer.
- Ambient temperature is known (Ta).
∴ Temperature rise = T – Ta is found.
- The rated voltage with rated frequency is applied in the circuit.
- A continuous current is passed till steady temperature is reached. The readings of temperature of various conducting , insulating and structure parts are taken every after 1/2 Hr or 1Hr.
- The maximum temperature of the parts shall be within the prescribed limits.
- The thermocouple comprises a junction of two dissimilar materials.
- The emf induced depends upon temperature difference between the hot junction and the cold end.
- The hot junctions on fixed on the parts of isolator (contacts of isolators, terminals insulators etc.)
- The output of thermocouple is measured by potentiometer or digital voltmeter.
- The temperature is calculated for the calibrated value (°C per Milivolts)
2. Mechanical Test (Endurance Test)
- This is for testing reliability of mechanical operation of isolator.
- The isolator contacts are opened and closed several times.
- The contacts are closed and opened by usual way (manual or motorized) After this test, all contacts, linkages, are thoroughly checked.
- The dimensions of all these should be in original limits.
- If any part has failed mechanically, the dimensions are out of permissible limits.
- Generally 1000 close-open cycles are specified in standards.